FireInspectorNear Inspection CalendarDue dates

Fire pumps and standpipes

The Alabama Department of Public Health weekly fire pump form, based on the 1998 edition of the national standard, says the listed inspections are all performed weekly.

Sources read October 7, 2026. Each section links the pages it came from.

Testing

The Alabama Department of Public Health weekly form asks whether an electric motor driven pump started automatically and ran for at least 10 minutes.

For diesel engine driven pumps, the Alabama form asks whether the pump ran for at least 30 minutes.

Clark County Fire Department in Nevada requires an operational permit for every fire pump and an annual submittal of the pump flow test results.

Clark County says the fire pump operational permit is issued to and kept by the building owner.

The Seattle Fire Department standpipe test report says a flow test is required every five years for all automatic standpipe systems.

The Seattle report also checks that manual dry and semi-automatic dry standpipes passed their 5-year hydrostatic test.

OSHA 1910.158(e)(2)(iii) requires standpipe hose systems to be inspected at least once a year and after each use.

Sources: Fire pumps are checked weekly; Annual fire pump flow test; Five year standpipe flow test; Hose systems inspected yearly

Common questions

How often is a fire pump tested?

Often weekly, plus a flow test once a year, though the schedule depends on the code your area adopted. Alabama's public health form lists weekly fire pump inspections, and Clark County, Nevada requires the annual flow test results.

Find inspectors Due dates