BEGIN:VCALENDAR
VERSION:2.0
PRODID:-//FireInspectorNear//Fire inspection reminders//EN
CALSCALE:GREGORIAN
METHOD:PUBLISH
X-WR-CALNAME:Fire inspection reminders (FireInspectorNear)
X-WR-TIMEZONE:America/Chicago
BEGIN:VEVENT
UID:ext_monthly@fireinspectornear.com
DTSTAMP:20261007T045225Z
DTSTART;VALUE=DATE:20261101
DTEND;VALUE=DATE:20261102
RRULE:FREQ=MONTHLY;INTERVAL=1
SUMMARY:Extinguisher visual check (owner) (every month)
DESCRIPTION:Under 29 CFR 1910.157\, portable extinguishers (or hose used i
 nstead) must be visually inspected every month. Source: https://www.osha.g
 ov/laws-regs/regulations/standardnumber/1910/1910.157 . This reminder star
 ts on 2026-11-01 and repeats every month. Move the first one to match the 
 date on your last inspection tag or report\, or make a file from your own 
 dates at https://fireinspectornear.com/tools/compliance-calendar/ . Your f
 ire marshal\, insurer or adopted code edition can set different dates. Lic
 ensed companies: https://fireinspectornear.com/find/
URL:https://fireinspectornear.com/tools/compliance-calendar/
END:VEVENT
BEGIN:VEVENT
UID:ext_annual@fireinspectornear.com
DTSTAMP:20261007T045225Z
DTSTART;VALUE=DATE:20261101
DTEND;VALUE=DATE:20261102
RRULE:FREQ=YEARLY;INTERVAL=1
SUMMARY:Extinguisher maintenance by a licensed company (every year)
DESCRIPTION:Employers must have extinguishers maintained annually and keep
  the maintenance date record for one year after the last entry or the life
  of the shell. Source: https://www.osha.gov/laws-regs/regulations/standard
 number/1910/1910.157 . This reminder starts on 2026-11-01 and repeats ever
 y year. Move the first one to match the date on your last inspection tag o
 r report\, or make a file from your own dates at https://fireinspectornear
 .com/tools/compliance-calendar/ . Your fire marshal\, insurer or adopted c
 ode edition can set different dates. Licensed companies: https://fireinspe
 ctornear.com/find/
URL:https://fireinspectornear.com/tools/compliance-calendar/
END:VEVENT
BEGIN:VEVENT
UID:ext_6yr@fireinspectornear.com
DTSTAMP:20261007T045225Z
DTSTART;VALUE=DATE:20261101
DTEND;VALUE=DATE:20261102
RRULE:FREQ=YEARLY;INTERVAL=6
SUMMARY:Extinguisher 6-year maintenance (stored pressure dry chemical) (ev
 ery 6 years)
DESCRIPTION:Stored pressure dry chemical extinguishers that need a 12 year
  hydrostatic test must be emptied and maintained every 6 years. Source: ht
 tps://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.157 . Th
 is reminder starts on 2026-11-01 and repeats every 6 years. Move the first
  one to match the date on your last inspection tag or report\, or make a f
 ile from your own dates at https://fireinspectornear.com/tools/compliance-
 calendar/ . Your fire marshal\, insurer or adopted code edition can set di
 fferent dates. Licensed companies: https://fireinspectornear.com/find/
URL:https://fireinspectornear.com/tools/compliance-calendar/
END:VEVENT
BEGIN:VEVENT
UID:ext_hydro5@fireinspectornear.com
DTSTAMP:20261007T045225Z
DTSTART;VALUE=DATE:20261101
DTEND;VALUE=DATE:20261102
RRULE:FREQ=YEARLY;INTERVAL=5
SUMMARY:Hydrostatic test (types on the 5-year cycle) (every 5 years)
DESCRIPTION:Hydrostatic testing is done every 5 or 12 years depending on e
 xtinguisher type. Source: https://www.nfpa.org/news-blogs-and-articles/blo
 gs/2020/10/30/guide-to-fire-extinguisher-itm . This reminder starts on 202
 6-11-01 and repeats every 5 years. Move the first one to match the date on
  your last inspection tag or report\, or make a file from your own dates a
 t https://fireinspectornear.com/tools/compliance-calendar/ . Your fire mar
 shal\, insurer or adopted code edition can set different dates. Licensed c
 ompanies: https://fireinspectornear.com/find/
URL:https://fireinspectornear.com/tools/compliance-calendar/
END:VEVENT
BEGIN:VEVENT
UID:ext_hydro12@fireinspectornear.com
DTSTAMP:20261007T045225Z
DTSTART;VALUE=DATE:20261101
DTEND;VALUE=DATE:20261102
RRULE:FREQ=YEARLY;INTERVAL=12
SUMMARY:Hydrostatic test (types on the 12-year cycle) (every 12 years)
DESCRIPTION:Hydrostatic testing is done every 5 or 12 years depending on e
 xtinguisher type. Source: https://www.nfpa.org/news-blogs-and-articles/blo
 gs/2020/10/30/guide-to-fire-extinguisher-itm . This reminder starts on 202
 6-11-01 and repeats every 12 years. Move the first one to match the date o
 n your last inspection tag or report\, or make a file from your own dates 
 at https://fireinspectornear.com/tools/compliance-calendar/ . Your fire ma
 rshal\, insurer or adopted code edition can set different dates. Licensed 
 companies: https://fireinspectornear.com/find/
URL:https://fireinspectornear.com/tools/compliance-calendar/
END:VEVENT
BEGIN:VEVENT
UID:hood@fireinspectornear.com
DTSTAMP:20261007T045225Z
DTSTART;VALUE=DATE:20261101
DTEND;VALUE=DATE:20261102
RRULE:FREQ=MONTHLY;INTERVAL=6
SUMMARY:Kitchen hood suppression maintenance (every 6 months)
DESCRIPTION:An NFPA blog on restaurants says\, citing NFPA 96\, that kitch
 en fire extinguishing systems must be maintained at least every 6 months. 
 Source: https://www.nfpa.org/news-blogs-and-articles/blogs/2021/04/27/rest
 aurant-fire-protection-basics . This reminder starts on 2026-11-01 and rep
 eats every 6 months. Move the first one to match the date on your last ins
 pection tag or report\, or make a file from your own dates at https://fire
 inspectornear.com/tools/compliance-calendar/ . Your fire marshal\, insurer
  or adopted code edition can set different dates. Licensed companies: http
 s://fireinspectornear.com/find/
URL:https://fireinspectornear.com/tools/compliance-calendar/
END:VEVENT
BEGIN:VEVENT
UID:sprinkler_q@fireinspectornear.com
DTSTAMP:20261007T045225Z
DTSTART;VALUE=DATE:20261101
DTEND;VALUE=DATE:20261102
RRULE:FREQ=MONTHLY;INTERVAL=3
SUMMARY:Sprinkler control valves (quarterly if supervised) (every 3 months
 )
DESCRIPTION:An NFPA blog table on NFPA 25 frequencies lists sprinkler cont
 rol valve inspection monthly if locked and quarterly if electrically super
 vised. Source: https://www.nfpa.org/News-and-Research/Publications-and-med
 ia/Blogs-Landing-Page/NFPA-Today/Blog-Posts/2021/11/05/Importance-of-Inspe
 ction-Testing-and-Maintenance-of-Fire-Protection-Systems . This reminder s
 tarts on 2026-11-01 and repeats every 3 months. Move the first one to matc
 h the date on your last inspection tag or report\, or make a file from you
 r own dates at https://fireinspectornear.com/tools/compliance-calendar/ . 
 Your fire marshal\, insurer or adopted code edition can set different date
 s. Licensed companies: https://fireinspectornear.com/find/
URL:https://fireinspectornear.com/tools/compliance-calendar/
END:VEVENT
BEGIN:VEVENT
UID:sprinkler_a@fireinspectornear.com
DTSTAMP:20261007T045225Z
DTSTART;VALUE=DATE:20261101
DTEND;VALUE=DATE:20261102
RRULE:FREQ=YEARLY;INTERVAL=1
SUMMARY:Sprinkler inspection (annual report) (every year)
DESCRIPTION:Nashville's fire marshal requires service companies to report 
 their inspections online\, and the report types it lists include annual sp
 rinkler inspection\, annual fire alarm and semi-annual hood suppression. S
 ource: https://www.nashville.gov/departments/fire/fire-marshal-office/insp
 ection-reports-online . This reminder starts on 2026-11-01 and repeats eve
 ry year. Move the first one to match the date on your last inspection tag 
 or report\, or make a file from your own dates at https://fireinspectornea
 r.com/tools/compliance-calendar/ . Your fire marshal\, insurer or adopted 
 code edition can set different dates. Licensed companies: https://fireinsp
 ectornear.com/find/
URL:https://fireinspectornear.com/tools/compliance-calendar/
END:VEVENT
BEGIN:VEVENT
UID:alarm@fireinspectornear.com
DTSTAMP:20261007T045225Z
DTSTART;VALUE=DATE:20261101
DTEND;VALUE=DATE:20261102
RRULE:FREQ=YEARLY;INTERVAL=1
SUMMARY:Fire alarm inspection (annual report) (every year)
DESCRIPTION:Nashville's fire marshal requires service companies to report 
 their inspections online\, and the report types it lists include annual sp
 rinkler inspection\, annual fire alarm and semi-annual hood suppression. S
 ource: https://www.nashville.gov/departments/fire/fire-marshal-office/insp
 ection-reports-online . This reminder starts on 2026-11-01 and repeats eve
 ry year. Move the first one to match the date on your last inspection tag 
 or report\, or make a file from your own dates at https://fireinspectornea
 r.com/tools/compliance-calendar/ . Your fire marshal\, insurer or adopted 
 code edition can set different dates. Licensed companies: https://fireinsp
 ectornear.com/find/
URL:https://fireinspectornear.com/tools/compliance-calendar/
END:VEVENT
BEGIN:VEVENT
UID:lights_m@fireinspectornear.com
DTSTAMP:20261007T045225Z
DTSTART;VALUE=DATE:20261101
DTEND;VALUE=DATE:20261102
RRULE:FREQ=MONTHLY;INTERVAL=1
SUMMARY:Emergency lights and exit signs: monthly test (every month)
DESCRIPTION:The Kansas State Fire Marshal says all emergency lights must b
 e tested for 30 seconds every month and for 90 minutes once a year. Source
 : https://firemarshal.ks.gov/DocumentCenter/View/1517/Emergency-Lighting .
  This reminder starts on 2026-11-01 and repeats every month. Move the firs
 t one to match the date on your last inspection tag or report\, or make a 
 file from your own dates at https://fireinspectornear.com/tools/compliance
 -calendar/ . Your fire marshal\, insurer or adopted code edition can set d
 ifferent dates. Licensed companies: https://fireinspectornear.com/find/
URL:https://fireinspectornear.com/tools/compliance-calendar/
END:VEVENT
BEGIN:VEVENT
UID:lights_a@fireinspectornear.com
DTSTAMP:20261007T045225Z
DTSTART;VALUE=DATE:20261101
DTEND;VALUE=DATE:20261102
RRULE:FREQ=YEARLY;INTERVAL=1
SUMMARY:Emergency lights: annual 90-minute test (every year)
DESCRIPTION:The Kansas State Fire Marshal says all emergency lights must b
 e tested for 30 seconds every month and for 90 minutes once a year. Source
 : https://firemarshal.ks.gov/DocumentCenter/View/1517/Emergency-Lighting .
  This reminder starts on 2026-11-01 and repeats every year. Move the first
  one to match the date on your last inspection tag or report\, or make a f
 ile from your own dates at https://fireinspectornear.com/tools/compliance-
 calendar/ . Your fire marshal\, insurer or adopted code edition can set di
 fferent dates. Licensed companies: https://fireinspectornear.com/find/
URL:https://fireinspectornear.com/tools/compliance-calendar/
END:VEVENT
END:VCALENDAR